GE Security's Picture Perfect™ Flags and Values, Picture Perfect 1.5-2.0
This table shows the meanings and value meanings for all of the bit fields in the GE Security CASI Picture Perfect database.
| Bit Meaning | Bit Number | Meaning When 0 | Meaning When 1 | |
|---|---|---|---|---|
| alarm.flags | ||||
| Micro internal use only
| 0
| Off
| On
| |
| Online
| 1
| No
| Yes
| |
| Schedule Inhibit
| 2
| No
| Yes
| |
| Auto Reset Outputs
| 3
| No
| Yes
| |
| Manual Reset Outputs
| 4
| No
| Yes
| |
| Duration Reset Outputs
| 5
| No
| Yes
| |
| Immediate Reset Input
| 6
| No
| Yes
| |
| Immediate Dial Required
| 7
| No
| Yes
| |
| area.flags | ||||
| Logical State
| 0
| Offline
| Online
| |
| Physical
| 1
| Disabled
| Enabled
| |
| Shunting
| 2
| Disabled
| Enabled
| |
| | Scheduling
| 3
| Enabled
| Disabled
|
| APB Enforcement
| 4
| Normal
| Passive
| |
| badge.flags | ||||
| Keypad Response
| 0
| Disabled
| Enable
| |
| Card Trace
| 1
| Disabled
| Enabled
| |
| Limited Usage
| 2
| Reserved
| Exhausted
| |
| Tour Badge
| 3
| No
| Yes
| |
| Temporary Badge*
| 4
| No
| Yes
| |
| inputs.flags | ||||
| Normally Closed
| 0
| No (Normally Open)
| Yes (Normally Closed)
| |
| Input Enabled
| 1
| No
| Yes
| |
| input_group.flags | ||||
| Not Used
| 0
| Not Used
| Not Used
| |
| Input Group State
| 1
| Disabled
| Enabled
| |
| Open Condition
| 2
| Ignored
| Detected
| |
| Short Condition
| 3
| Ignored
| Detected
| |
| Broadcast State Changes
| 4
| No
| Yes
| |
| output.flags | ||||
| Normally Open
| 0
| No
| Yes
| |
| Output Enabled
| 1
| No
| Yes
| |
| Reset On Duration
| 2
| No
| Yes
| |
| Reset On Input
| 3
| No
| Yes
| |
| permission.flags | ||||
| None
| 0
| No
| Yes
| |
| Read Only - Show Number
| 1
| No
| Yes
| |
| Read Only - Hide Number
| 2
| No
| Yes
| |
| Issue - Show Number
| 3
| No
| Yes
| |
| Issue - Hide Number
| 4
| No
| Yes
| |
| reader.type | ||||
| Badge Rdr
| 0
| No
| Yes
| |
| Badge and Keypad
| 1
| No
| Yes
| |
| Keypad Only Rdr
| 2
| No
| Yes
| |
| Badge or Keypad
| 3
| No
| Yes
| |
| ABP In Rdr
| 4
| No
| Yes
| |
| APB Out Rdr
| 5
| No
| Yes
| |
| For Future Use
| 6
| 0
|
| |
| T/A In and Out
| 7
| No
| Yes
| |
| T/A In Rdr
| 8
| No
| Yes
| |
| T/A Out Rdr
| 9
| No
| Yes
| |
| Authorization Required
| 10
| No
| Yes
| |
| No Authorization Required
| 11
| No
| Yes
| |
| reader.flags | ||||
| Logical State
| 0
| Offline
| Online
| |
| Physical State
| 1
| Disabled
| Enabled
| |
| Shunting
| 2
| Disabled
| Enabled
| |
| Scheduling
| 3
| Enabled
| Disabled
| |
| Toggle
| 4
| No
| Yes
| |
| Limited Usage
| 5
| Disabled
| Enabled
| |
| Elevator Reader
| 6
| No
| Yes
| |
| routing.flags | ||||
| Monitor
| 0
| No
| Yes
| |
| History
| 1
| No
| Yes
| |
| Printer
| 2
| No
| Yes
| |
| door.flags | ||||
| State
| 0
| Locked
| Unlocked
| |
| Scheduling
| 1
| Enabled
| Disabled
| |
| Held Open Sensing
| 2
| Ignored
| Detected
| |
| Forced Open Monitoring
| 3
| Ignored
| Detected
| |
| Exit Button Asserts Strike
| 4
| Disabled
| Enabled
| |
| Pre-Alarm
| 5
| Disabled
| Enabled
| |
| Keypad Alarm Response
| 6
| Disabled
| Enabled
| |
| Forced Relock
| 7
| Disabled
| Enabled
| |
| On Door Open
| 8
| Disabled
| Enabled
| |
| On Door Close
| 9
| Disabled
| Enabled
| |
| On Door Unlock Duration
| 10
| Disabled
| Enabled
| |
| * Picture Perfect 2.0 only
| ||||
| | ||||
| | ||||